Water saving fixtures (post 1991) less than 1.0 gal per flush water closets and 3.0 gpm faucets/showerheads - design flow = 90 GPD per bedroom.
System Components........Wells...........Dwelling
Septic tank......................50ft.............10ft
Distribution box..............100ft............20ft
Absorption field..............100ft*...........20ft
*when sewage treatment systems are located in coarse gravel or upgrade and in the general path of drainage to a well, the closest part of the treatment system shall be at least 200 feet away from the well.
1,2, or 3 bedrooms.........................1000 gallons
4 bedrooms....................................1250 gallons
Absorption field system -
e.g. A 4-bedroom home with 600 gal/day flow rate and 21-30 (min/inch) percolation rate requires 500 feet of trench.
Absorption trenches are constructed 18 to 30 inches below grade.
A minimum horizontal separation distance between parallel absorption trenches of 10', 9', 8' or 7' is provided when minimum vertical separation distance from the bottom of any absorption trench to high ground water, bedrock, or impermeable soil is 2', 3', 4' or 5', respectively.