Electrical Design:
Sizing conductors/ circuit breakers
- Sizing electric service
- Sizing grounding electrode conductor size
- General cable types
- Romex (nonmetallic sheathed cable)
- not in buildings >3 floors
- min. 1/4in sheathing into box
- protect from physical damage
- nail plate req'd when cable is 1 1/4in of stud edge
- Clamped to box with approved NM clamp
- max. bend radius(5 x diameter)
- staple within 12in. of box and every 4 1/2 ft
- BX (armor-clad cable)
- stapled min. every 4 1/2 ft. & within 12in. of box
- insulated bushing at terminations
- nail plate req'd where cable is 1 1/4 in. of stud face
- General Purpose Circuits
- Receptacles
- any wall>2ft. wide req's receptacle
- 6 ft. cord can be plugged in anywhere along wall
- hallway>10ft. req's receptacle
- Lights
- switched lighting outlets req'd in all habitable rooms,baths,halls,stairs
(3 way/>6 steps),garages,outdoor entrances,storage or utility area,attics,basements
- recessed light 3in. from insulation
- Paddle Fans
- not to be supported by standard electrical boxes
- Bathroom
- GFCI req'd adjacent to basin
- Bathroom receptacles req. separate 20A circuit
- Kitchen Circuits
- Two 20A small-appliance circuits req'd
- countertop-min. 2 small-appliance circuits
- no lighting permitted on these circuits
- counters>12in wide red. receptacles
- GFCI protection for all countertop receptacles
- GFCI-protect any receptacle within 6ft. of sink
- Appliances
- electric range-min. 40A wire (#8 copper)
- garbage disposal cord must be > 18in. but <36 in.
- garbage disposal/dishwasher on single duplex receptacle(3-wire 240V)
req's a tie-bar breaker
- dishwasher cord(under sink) 3-4ft. long
- plugs of fixed appliance accessible
- Utility
- Laundry
- separate 20A circuit req'd for laundry
- electric dryer min. feed 30A #10 THHN wire
- Gas Furnace
- fused (125%) disconnect (SSU switch)
- lighting outlet switched at entry req'd
- separate circuit
- 120V receptacle on the same level and within 25 ft.
- Water Heater
- in-sight disconnect
- bond hot,cold and gas pipes
- Heating Units
- branch circuit-125%
- maximum 48A unsubdivided load
- Air Conditioning
- window-unit cord and plug OK if controls are <6 ft. of the floor
- 120V window-unit cord max. 10 ft.
- Conduit Systems
- General Requirements
- openings to conduit system must remain accessible
- no common plastic boxes with metal raceway, BX or MC cable
- crimps(kinks) in pipe not permitted
- EMT (electrical metallic tubing)
- not approved for burial unless coated
- rain-tight fittings outside
- supported within 36 in. of any box and every 10ft.
- Flexible Metal Conduit
- dry locations only
- support min. every 4 1/2ft. & within 12in. of box
- angle connections may not be concealed
- Liquid-tight
- Boxes
- metal boxes grounded with approved method
- wallboard repaired-no gaps> 1/8 in. to outlet box
- boxes and conduits must remain accessible
- outlet boxes shall be flush with combustible surfaces
- min 6" of free conductor in box
- Garage
- min one lighting outlet & one GFCI receptacle req'd
- all receptacles GFCI-protected except single receptacle,inaccessible behind a fixed appliance
- subpanels shall not penetrate modified 1hr. wall
- detached garage req'd grounding electrode
- Outdoors
- receptacles at grade front & rear GFCI-protected
- doors to outside req. lighting outlet
- rain-tight cover for unattended cords
- boathouse receptacles must be GFCI-protected
- Closet
- enclosed incandescent-12in. of clearance
- surface fluorescent or recessed incandescent- 6in.
- no open incandescent bulb-type fixtures
- no new breaker panels